Bulahdelah Showground, Power Reticulation Site Upgrade.
Business Name
Mid Coast Council
VP Reference #
VP436995
Buyers Reference #
MCC-24-026
Opens
Monday 11 November 2024
(AUS Eastern Standard Time)
Closes
Thursday 12 December 2024 11:00 AM
(AUS Eastern Standard Time)
CLOSED
Supplier query cut-off
Tuesday 10 December 2024 11:00 AM
(AUS Eastern Daylight Time)
Expected decision
Thursday 19 December 2024
(AUS Eastern Standard Time)
Buyer Details
Business Name
Mid Coast Council
Location
2 Biripi Wy
Taree, New South Wales 2430
Australia
WebSite:
http://www.midcoast.nsw.gov.au
Business Info
The merger of Gloucester Shire, Great Lakes and Greater Taree City councils
Contact Name
Mollyrose Simmons
Position:
Project Manager
Primary phone:
0279557245
Mobile phone:
0439364021
Fax number:
None Provided
Email:
mollyrose.simmons@midcoast.nsw.gov.au
What the buyer is requesting
Details
The work consists of, but is not necessarily limited to the supply, installation, and commissioning of the following: power reticulation system, switchboards & distribution boards. If the existing condition does not conform to the requirements in the contract documents, submit proposals to rectify the deficiencies with related costing, time and other impacts. This project aims to enhance the power infrastructure to meet load demands and reduce risks from aging services by adhering to current codes and standards, benefiting all area users.
Please direct all your technical enquiries to:
Senior Electrician,
Stephen Camilleri - +61 409 816 058
Background information / Compatibility requirements
Details
The design, supply, installation and commissioning of all mains cables, submains cables, Switchgear and Switchboards, and removal of redundant cabling.
The below criteria apply and should be considered in tender:
• Execute STAGE ONE of the Bulahdelah Showground site reticulation upgrade – Power Reticulation System, Switchboards and Distribution Boards.
Desired Outcomes ('Nice to haves', Conditions & Warranties, SLA's, Project benefits)
Details
Provide an electrical system and elements that are suitable for the ambient service conditions and operating environment with components and equipment suitable for the system application.
Note: The showground is still in operation so existing electrical supplies to existing occupied areas are to be maintained. All interruptions to services are to be coordinated and approved by Midcoast council.
Supplier lists selected
Lists
ELEC, Lighting, Equip & Services
Electronic Components & Supplies
Categories selected
Categories
Electrical Systems, Lighting, Equipment & Services
1: Electrical Equipment & Components & Supplies
2: Electrical Services
3: Electrical Wire & Cable & Harness
4: Electrical Wire Management Devices & Accessories
5: Lighting & Light Poles
6: Switchboards & Switchgear
7: Testing & Tagging
Electronic Components & Supplies
1: Electronic Components & Supplies
Regions of Service
Locations
New South Wales
1: Mid-North Coast
All Regions of Service locations are within Australia.
Information requested by others
15/Nov/2024 08:46 PM
Question
:
what are the emergency utilities the back up generator needs to supply?
Conduit and cabling provisions to support the future installation of 2 additional ring pole lights center to arena at the North and South ends. is this suppose to be stage 3? if not can you mark up on the plans so we know where this needs to go
Answered on 26/Nov/2024 11:00 AM
:
1. The Generator / Back up Supply are to allow sufficient supply to feed the Pavillion and Public Amenities as emergency utilities.
2. Provisions for the trenching and conduits are to be included in stage one for the 2 light rings at N and S ends of arena. All additional works such as additional cabling, footings etc can be addressed in Stage 2 costings.
25/Nov/2024 09:46 AM
Question
:
Good morning,
We will be attending the pre-tender meeting at 11.00am on Monday 2nd December.
Answered on 26/Nov/2024 10:29 AM
:
Thank you, i have registered your interest
28/Nov/2024 01:08 PM
Question
:
Attention: Mollyrose Simmons
SYSCON wish to advise we will be attending the non-mandatory site inspection on Monday 2/12/2024
Attendees:
* Brendan Mobbs
* Rick Atchison
* Joshua Hocking
Regards
Brendan Mobbs
Answered on 29/Nov/2024 07:34 AM
:
Registered. Thank you
03/Dec/2024 02:58 PM
Question
:
On the plan E02 is shows the Lions shed, stage & broadcast box are included on stage 1 (in red) however on plan E01 it's not highlighted with any stage. Can you please confirm if this is just a reconnection in stage 1 or does it require new undergrounds as stated in E02.
Answered on 04/Dec/2024 06:17 AM
:
(edited on 04/Dec/2024 06:21 AM)
Q1:
Please allow for new undergrounds as stated in E02. As per the Single Line & Control Diagrams please treat these works as part of Stage 1.
Additional Questions:
Q2:
"The Consumers Mains that are on the Single Line & Control Diagrams as 70mmsq X-90 Copper cables are not rated for the 200 Amp Supply (the 70mmsq cable is rated at 142 Amps “Wiring Enclosure in Air” and 170 Amps “Underground Wiring Enclosure”.) Minimum Size Cable would be 120mmsq Copper X-90 Cable rated at 202 Amps “Wiring Enclosure in Air” and 237 Amps “Underground Wiring Enclosure”.
Answer:
EPA Energy have realised the issue as we have inadvertently sized these based on them being a service main and not a consumer’s mains, as 200A service mains have designated cable sizes that must be used, which is 70sqmm.
As these are a consumer’s mains and not a service main, then we can use a cable based on the rating, which in this case should be 120sqmm X90 cable not 70sqmm X-90 cable.
So please be advised that the mains cables should 4 x1C 120sqmm X-90 cable.
Updated IFC Drawings will be provided post tender award.
Q3:
Will the Halytech Illuminator Controller be supplied by MCC or are we to Supply and Install?
Answer:
Halytech Illuminator Controller to be supplied and installed by contractor.
04/Dec/2024 08:51 AM
Question
:
Question 1 - Can you please confirm if the 120mm X-90 cable is from the fuses on the private pole above the MSB?
Question 2 - Will there be updated MSB drawings to reflect the request for a generator change over switch. None of this is stated in E02.
Answered on 04/Dec/2024 09:43 AM
:
Question 1 - Confirmed by EPA Energy
Question 2 - Yes, this will be illustrated in IFC Drawing Set as mentioned in Tender Clarifications Letter
04/Dec/2024 08:57 AM
Question
:
Question 1 -
You have stated in another question we need to now re-feed the Stage4 and Broad cast box. is this using existing conduits and just installing new Cabling? Or re-trenching with new conduits. When onsite the electricians had informed us to just re-connect the existing services. Can you please clarify.
Answered on 04/Dec/2024 09:32 AM
:
If existing services remain, please re-connect - Lions Shed, Kiosk and Bar.
Where there is new Supply, please allow for new Cable and Conduit - Broadcast Box.
05/Dec/2024 07:24 AM
Question
:
Hi, Do you have a photo of the 3rd camping power board that needs to be reinstalled. is there and engineering detail for its base concrete footing or is its footing still attached and re-useable?
Answered on 05/Dec/2024 01:20 PM
:
Photos will be attached as an addendum.
Please note the reinstatement of Power Board is simple - Post and Quickset Cement. Standard Install method is with 4 Bags of concrete mix.
05/Dec/2024 04:37 PM
Question
:
Generator connection was discussed on site with manual discrimination of energised circuits. Is a manual transfer switch required for this? will you require a lockable terminal box for generator connection or a socket arrangement. Can you please advise the maximum current provision for the generator connection?
Answered on 06/Dec/2024 09:32 AM
:
As per Clarifications attached in Addenda dated: 02.12.2024
32amp 3 Phase Generator Inlet/Outlet – To be plugged into including a changeover switch from the mains. MCC will then monitor and determine which circuits will be maintained (on/off)
Updates made to this Request
08/Nov/2024 01:49 PM
MCC-24-026 - Part A - Introduction and Conditions of Tendering.docx
MCC-24-026 - Part B - Specification (for construction or works types).cleaned.docx
MCC-24-026 - Part C - Minor Works - Construct Only DRAFT.docx
MCC-24-026 - Part D - Response Schedule.docx
MCC-24-026 - Part D - Schedule of Prices.xlsx
Please consider these attachments when responding.
02/Dec/2024 02:19 PM
Please note: The following addenda have been recently added.
1. Added: (Addendum) Drainage_ Sewer & Water Network Mapping.pdf
2. Added: (Addendum) ECM_16678207_v1_16000041 - PROPERTY MANAGEMENT (COUNCIL PROPERTY) - MAINTENANCE - Routine - 15 11 2023 - ACM Report.pdf
Following today's site meeting, please consider these addenda when responding.
02/Dec/2024 02:31 PM
Please note: The following addendum has been recently added.
1. Added: (Addendum) 2.12.24 Bulahdelah Showground Power Reticulation Upgrade Minutes - Clarifications.pdf
Please consider this addendum when responding.
05/Dec/2024 01:22 PM
Please note: The following addenda have been recently added.
1. Added: (Addendum) IMG_2287.JPG
2. Added: (Addendum) Resized_20241205_124044.JPEG
3. Added: (Addendum) Resized_20241205_124053.JPEG
Please consider these addenda when responding.
05/Dec/2024 01:23 PM
Please note: The following addenda have been recently added.
1. Added: (Addendum) IMG_2287.JPG
2. Added: (Addendum) Resized_20241205_124044.JPEG
3. Added: (Addendum) Resized_20241205_124053.JPEG
Please consider these addenda when responding.
05/Dec/2024 01:23 PM
Please note: The following addenda have been recently added.
1. Added: (Addendum) IMG_2287.JPG
2. Added: (Addendum) Resized_20241205_124044.JPEG
3. Added: (Addendum) Resized_20241205_124053.JPEG
Please consider these addenda when responding.