Mackay Turf Club Jockey & Steward Room & Swab Box Upgrade
Business Name
Racing Queensland
VP Reference #
VP519485
Buyers Reference #
RQ04961
Opens
Monday 03 August 2026 (E. Australia Standard Time)
Closes
Friday 11 September 2026 02:00 PM (E. Australia Standard Time) CLOSED
Supplier query cut-off
Wednesday 09 September 2026 02:00 PM (E. Australia Standard Time)
Expected decision
Friday 23 October 2026 (E. Australia Standard Time)
Buyer Details
Business Name
Racing Queensland
Location
2 Racecourse Rd
Deagon, Queensland 4017
Australia
WebSite:
https://www.racingqueensland.com.au
Business Info
The Racing Queensland Board trading as Racing Queensland provides a platform to service the racing industry across the three codes of racing.
Racing Queensland's vision is to be the #1 sporting industry in the sunshine state. Our purpose is to connect Queenslanders through great racing, events and the love of our animals.,The Racing Queensland Board trading as Racing Queensland provides a platform to service the racing industry across the three codes of racing.
Racing Queensland's vision is to be the #1 sporting industry in the sunshine state. Our purpose is to connect Queenslanders through great racing, events and the love of our animals.,The Racing Queensland Board trading as Racing Queensland provides a platform to service the racing industry across the three codes of racing.
Racing Queensland's vision is to be the #1 sporting industry in the sunshine state. Our purpose is to connect Queenslanders through great racing, events and the love of our animals.
Contact Details
The buyer has elected to have their personal and contact details hidden. These details will be revealed at the buyers discretion.
What the buyer is requesting
Details
Dear Tenderer,

Letter of Invitation – RQ04961 – Mackay Turf Club Jockey & Steward Room & Swab Box Upgrade

Racing Queensland (RQ) is seeking offers from suitably experienced Suppliers for the renovation and extension of the existing jockey & steward facilities and the construction of a new dual swab box at the Mackay Turf Club Inc.

The successful supplier will be engaged via Racing Queensland’s Works Agreement.

The following documentation is available to be downloaded via VendorPanel (VP519485):

• This Letter of Invitation;

• Scope of Works document;

• Appendix documents A-E (x5);

• Tender Response Schedule (returnable);

• Price Response Schedule (returnable);

• RQ Works Agreement TEMPLATE;

• RQ Conditions of Tendering; and

• Queensland Government Supplier Code of Conduct 2026.

Offers may only be submitted electronically through VendorPanel, no later than 2pm (AEST) on Friday 11th September 2026. The closing time and date nominated in this Request for Tender (RFT) is the latest time by which a submission must be logged. Late submissions will NOT be accepted.

**********

An optional site inspection will be held at Mackay Turf Club on the following date:

- Tuesday, 25th August at 9am

Suppliers interested in attending a site inspection must email procurement@racingqueensland.com.au as soon as possible. We kindly as that, if you have expressed interest in attending, you email the names of representative(s) attending no later than two business days prior to the scheduled site inspection.

**********

Please direct all Tender related questions or clarifications in writing to Racing Queensland’s Procurement Team via VendorPanel.

We look to receiving your Tender submission.

Yours sincerely,

Lori Duggan

Specialist Procurement; Racing Queensland
Questions asked by the buyer
Question 1 - [Required]
Have you completed and submitted all Tender response documents?
Question 2 - [Required]
Has the Tender Response Schedule been signed by an appropriate delegate?
Question 3 - [Required]
Have all the mandatory criteria been met for your tender to be considered conforming?
Question 4 - [Required]
Have you provided copies of all relevant licences and insurances?
Question 5 - [Required]
Have you read and acknowledged all clarifications, RFIs, and addenda posted for this tender (if any)?
Supplier lists selected
Lists
  • Construction & Operation
Categories selected
Categories
  • Construction & Operation
    1: Building Construction Materials & Services
Regions of Service
Locations
  • Queensland
    1: Mackay

All Regions of Service locations are within Australia.
Information requested by others
31/Aug/2026 12:28 PM
Question:
I have a few questions relating to the electrical scope for the Mackay Turf Club tender.

What size are the proposed portable heated spas? What electrical specs are available to allow for correct sizing of cabling and outlets for connection.

On the proposed Jockey facilities electrical plans there are 2 x meter panels shown on the western wall. Is this correct or will one be sufficient?

Are the existing meter panels being reused? If not are there any specs on what meter board/s is required to be installed? What size board/s?

Do the exhaust fans require ducting/venting? Are there specific exhaust fans that need to be used?

What size, brand are the ceiling fans?

What wattage flood light is required?

Are the 2 x 20A 3 phase outlets on the eastern wall remaining in place and do they need to be replaced during the upgrades? If so is a specific brand required?

Is the solar system getting upgraded during works and will a solar contractor need to be included as part of the electrical scope?

Is the comms cabinet located on the eastern wall of the jockey facilities? Does the data cabling in the jockey facility go back to that point?

Are there any specifications for sizing of sub main cabling for the proposed Horse Drug Testing Building?

Will the sub main cabling for the Horse Drug Testing Facility nee to be installed underground or overhead?

Answered on 31/Aug/2026 02:28 PM:


Please see below answers (A) to your questions (Q):

Q1: What size are the proposed portable heated spas? What electrical specs are available to allow for correct sizing of cabling and outlets for connection.

A1: As per designs supplied min 2m x 1.5m capable of heating to 40 degrees. Cabling to be sized according to selected unit.

Q2: On the proposed Jockey facilities electrical plans there are 2 x meter panels shown on the western wall. Is this correct or will one be sufficient?

A2: As per supplied design, meter panels to be relocated from existing position to proposed positions. Vendors may choose after suitable consultation with electrical specialist to replace western wall with a singular meter board.

Q3: Are the existing meter panels being reused? If not are there any specs on what meter board/s is required to be installed? What size board/s?

A3: As above and supplied design.

Q4: Do the exhaust fans require ducting/venting? Are there specific exhaust fans that need to be used?

A4: Standard exhaust fans vented to roof cavity.

Q5: What size, brand are the ceiling fans?

A5: Standard builders range fans 122cm.

Q6: What wattage flood light is required?

A6: Min 100w (LED version).

Q7: Are the 2 x 20A 3 phase outlets on the eastern wall remaining in place and do they need to be replaced during the upgrades? If so, is a specific brand required?

A7: To remain unless unserviceable upon inspection by electrician at which point replacement only. This is power supply for SKY TV Trucks.

Q8: Is the solar system getting upgraded during works and will a solar contractor need to be included as part of the electrical scope?

A8: As per supplied design and Scope, existing solar to be removed and reinstalled in position as required for new roof. Nil upgrades unless required under electrical code.

Q9: Is the comms cabinet located on the eastern wall of the jockey facilities? Does the data cabling in the jockey facility go back to that point?

A9: Correct

Q10: Are there any specifications for sizing of sub main cabling for the proposed Horse Drug Testing Building?

A10: To be sized according to proposed load.

Q11: Will the sub main cabling for the Horse Drug Testing Facility need to be installed underground or overhead?

A11: Preferably underground.
31/Aug/2026 01:59 PM
Question:
Could you also please confirm if the downlights in the proposed Swab box need to be able to take a fluorescent/LED bulb rather than being a standard diffused LED downlight.

Do all batten lights around the outside of the buildings need to be of the weatherproof variety?

Answered on 31/Aug/2026 02:29 PM:


Please see below answers (A) to your questions (Q):

Q12: Could you also please confirm if the downlights in the proposed Swab box need to be able to take a fluorescent/LED bulb rather than being a standard diffused LED downlight.

A12: Downlights may be LED variety.

Q13: Do all batten lights around the outside of the buildings need to be of the weatherproof variety?

A13: External batten lights to be weatherproof.
Updates made to this Request
14/Aug/2026 09:03 AM
Please note that the optional site visit information has been added to the Details section of this request.

25/Aug/2026 02:09 PM
Please note: The following attachments have been recently added.

1. Added: Development Application Approval Notice.zip

2. Added: RQ04961 - Clarification 1 - 25.08.2026.pdf

3. Added: Existing Plumbing & Drainage As-Built.zip

Please consider these attachments when responding.