Tender Details
RFT-48 - Marrickville Golf Club Upgrade
Business Name
Inner West Council
VP Reference #
VP527102
Buyers Reference #
RFT 48
Opens
Thursday 24 September 2026
(AUS Eastern Standard Time)
Closes
Thursday 22 October 2026 05:00 PM
(AUS Eastern Standard Time)
CLOSED
Supplier query cut-off
Monday 19 October 2026 05:00 PM
(AUS Eastern Daylight Time)
Expected decision
Thursday 19 November 2026
(AUS Eastern Standard Time)
Buyer Details
Business Name
Inner West Council
Location
15 Unwins Bridge Rd
St Peters, New South Wales 2044
Australia
WebSite:
http://www.innerwest.nsw.gov.au/
Business Info
On the 12th May 2016 Ashfield, Leichhardt and Marrickville councils were merged into a new council, known as the Inner West Council, by the NSW State Government under their reform program for councils. The proclamation from the NSW State Government carries over the codes, plans, strategies and policies of former councils, and makes them the codes, plans, strategies and policies of the new council. This is to ensure that the new council continues to have codes, plans, strategies and policies in place to guide its operation.
Contact Details
The buyer has elected to have their personal and contact details hidden. These details will be revealed at the buyers discretion.
What the buyer is requesting
Details
Please see attached documentation.
Supplier lists selected
Lists
Construction & Operation
Categories selected
Categories
Construction & Operation
1: Building Construction Materials & Services
2: Demolition Services
3: Other Civil Construction Materials & Services
Regions of Service
Locations
New South Wales
1: Hunter
2: Illawarra
3: South Eastern
4: Sydney
All Regions of Service locations are within Australia.
Information requested by others
25/Sep/2026 11:24 AM
Question
:
Hi
Can you confirm pre-tender brief date and time.
Answered on 28/Sep/2026 02:05 PM
:
Apologies it was a typo: New Briefing date:
Thursday 1 October 2026 @ 8.30am .
28/Sep/2026 07:34 AM
Question
:
Can you please confirm the mandatrory briefing time & closing date.
RFT says 28 Oct for the briefing and 22 Oct for closing date.
Answered on 28/Sep/2026 02:05 PM
:
Apologies it was a typo: New Briefing date:
Thursday 1 October 2026 @ 8.30am .
28/Sep/2026 08:52 AM
Question
:
is the site visit today? Documents say Oct
Answered on 28/Sep/2026 02:05 PM
:
Apologies it was a typo: New Briefing date:
Thursday 1 October 2026 @ 8.30am .
28/Sep/2026 10:00 AM
Question
:
When is the site briefing? Schedule 1 states 10am 28 October, but this is after the closing date of 22 October. Thanks.
Answered on 28/Sep/2026 02:06 PM
:
Apologies it was a typo: New Briefing date:
Thursday 1 October 2026 @ 8.30am .
28/Sep/2026 04:03 PM
Question
:
Hi,
As the briefing today was mandatory and an additional mandatory site meeting has been organized for Thursday morning, can you please confirm if the Head Contractors that attended today need to reattend on Thursday due to the rescheduled time or if our attendance today qualifies us to submit our tender.
Thanks.
Answered on 28/Sep/2026 04:10 PM
:
Contractors who attended either of the mandatory site inspections (either Monday 28/9/26 (today) or Thursday 1/10/26) will qualify to submit a tender.
28/Sep/2026 04:57 PM
Question
:
Can you please confirm when would be the date of inspection?
Answered on 29/Sep/2026 08:45 AM
:
Briefing date: Thursday 1 October 2026 @ 8.30am.
29/Sep/2026 09:37 AM
Question
:
I just wanted to confirm that the mandatory meeting is in fact mandatory for either Monday or Thursday or both if we want.
Answered on 29/Sep/2026 09:56 AM
:
Yes, attendance to at least one of the meetings is required, but you can attend both.
29/Sep/2026 09:38 AM
Question
:
Good morning IWC,
We will be attending the site briefing on 1/10/26.
Our team will consist of our GM, PM, SM and AQM.
Can we bring trades along to this visit?
Kind regards,
James
Answered on 29/Sep/2026 10:00 AM
:
Yes you can, but the briefing is more for head contractors. We will be holding specific trades visit scheduled for 9am on Wednesday 7 October.
29/Sep/2026 04:57 PM
Question
:
Following the site walkthrough yesterday with Head Contractors and discussion around trade walkthrough. Could you please confirm trade walkthrough date of Wednesday 7th of Oct at 8:30am?
Answered on 30/Sep/2026 11:56 AM
:
We will be holding specific trades visit scheduled for 9am on Wednesday 7 October.
30/Sep/2026 02:48 PM
Question
:
Is the additional site briefing happening as scheduled on Thursday 1 October 2026 at 8.30am ? Did I miss a briefing on the 28.9.26?
Answered on 30/Sep/2026 03:14 PM
:
Yes there is a second site briefing Thursday 1.10.26 at 8.30am.
06/Oct/2026 10:04 AM
Question
:
Good morning - confirming that tomorrows site subcontractor walk through is still on for 9am tomorrow
Answered on 06/Oct/2026 11:21 AM
:
Yes that is confirmed.
07/Oct/2026 11:52 AM
Question
:
Hello
We intend to submit a tender for RFT-48 Marrickville Golf Club Upgrade.
We attended the site walkthrough held today, Wednesday 7 October at 9:00am.
Could you please confirm that our attendance at today's site walkthrough satisfies the site briefing attendance requirement and that we are eligible to submit a conforming tender?
Kind regards
Answered on 07/Oct/2026 12:28 PM
:
The trades walk through today Wednesday 7 October 2026 at 9am was a follow up walkthrough for tenderers who attended one of the mandatory site briefings, to bring their trades through.
This was not one of the mandatory site briefings that was held on either 29 September or 1 October 2026. If you did not attend one of those briefings, your tender will be considered non-compliant.
07/Oct/2026 04:56 PM
Question
:
No lighting schedule in the package, can you please confirm the specs?
No details for landscaping items, can you please confirm the specs?
TZ-01 cannot be found in drawings, please advise?
There's no pricing breakdown in the returnable schedule, can you please confirm if there's any BOQ or format to follow?
Answered on 08/Oct/2026 11:04 AM
:
The current package is a 75% detailed design package, hence there is some detail missing.
An updated 95% package will be uploaded to Vendor panel within the next 24 hours, with the below details included.
A pricing schedule was uploaded to vendor panel last week, however an updated version will be released with the new design package.
09/Oct/2026 08:53 AM
Question
:
Morning,
Question from one of our Contractors.
Are we only doing the ceilings, wall and bulkhead in the following areas: Restaurant Dining Space, Bar, Office, Community Room and Proshop? Suspended ceiling needed?
Assume Square set for windows/door?
Only Proshop the new building need wall insulation? How about the roof insulation?
Answered on 09/Oct/2026 09:57 AM
:
Are we only doing the ceilings, wall and bulkhead in the following areas: Restaurant Dining Space, Bar, Office, Community Room and Proshop? Suspended ceiling needed?
Refer to A-01-1500 for extent of new PB-01 / ACP-01 ceilings. No new ceiling to the office.
Pro shop will have a suspended ceiling but could also be framed between timber ceiling purlins if simpler.
Lockers and Staff Lunchroom will have a plasterboard ceiling.
Rondo Keylock suspended ceiling system captured in Arch Schedules.
Assume Square set for windows/door?
Painted Finger jointed pine reveals internally, refer A-01-5001 and A-02-4002/03
Only Proshop the new building need wall insulation? How about the roof insulation?
Refer to wall types schedule on A-01-1401 and arch schedules for existing club wall insulation. Acoustic insulation required between community room and restaurant. Ceiling insulation (INS-02) required above new ceilings in club.
Roof insulation in Pro shop building limited to pro shop and staff lunchroom.
09/Oct/2026 11:36 AM
Question
:
Morning Team,
As we have just received ALL updated documents and plans, we have had a few of our contractors / suppliers ask for and extension of 1 week.
Im sure there will be more questions asked in the coming days.
Please advise.
Answered on 12/Oct/2026 10:12 AM
:
Given the tight timing and the need to get this to council meeting for approval with a view to start Jan 2027, an extension is not possible.
09/Oct/2026 11:37 AM
Question
:
Hi Bill,
I just have a few questions regarding the scope of works for the golf course project.
Fire Service: For the new 150mm fire line, will we be responsible for all works, including connecting to the street main? Or will the new 100mm line be brought in from the street to the property boundary for us to connect to?
External Civil Works (Stormwater): Will all external stormwater works be included in our scope?
Excavation & Backfilling: For the external fire and stormwater works, will we be responsible for all excavation, or will a separate civil contractor be assisting with this? Also, will we be required to supply the blue metal and sand for bedding and backfilling around our pipework?
Downpipes: Can you please confirm whether the downpipes are specified to be PVC?
Just looking to clarify these items so we can accurately allow for everything in our scope of works.
Answered on 12/Oct/2026 10:13 AM
:
Fire works
All works for the water line including 150mm, 100mm line and connecting into the main will be the contractors responsibility. IWC will provide approvals to cross the viva, Ampol and Jemena lines on Beauchamp road only.
Civil
Yes all external storm water is included in scope as per plans.
Back filling and excavation.
Yes it is the contractors responsibility to supply and install bedding requirements as per relevant Australian standards and NCC.
Downpipes
Yes all Pennie's to be pvc as per specifications.
09/Oct/2026 02:45 PM
Question
:
Hi Andrew,
Could Council please advise whether a site walk-through of the Marrickville Golf Club works area can be arranged for tenderers before the close? If so, could you please let us know the available dates and times and the site contact.
Thanks,
Tiffany Cole
Estimating, Weyn Constructions
Answered on 12/Oct/2026 10:15 AM
:
Additional site visits can be arranged.
Monday and Wednesday AM preferred.
This can be arranged via vendor panel.
Please note: only tenderers who have already attended one or both of the mandatory site briefings will comply with tender requirements.
12/Oct/2026 07:16 AM
Question
:
Air-conditioning to the following areas?
Pro shop – Yes
Lockers –
Staff lunchroom – Yes
Garage – no
Do they have a preferred condensor location? On the roof?
Answered on 13/Oct/2026 10:47 AM
:
Air-conditioning to the following areas?
Pro shop – YES
Lockers – NO
Staff lunchroom – NO
Garage – NO
Condenser location to follow
13/Oct/2026 05:28 PM
Question
:
No mechanical drawings in the package, can you please confirm?
Answered on 14/Oct/2026 03:17 PM
:
No mechanical drawings as there are just split systems in the following areas:
Dinning room
Bar
Proshop
Please refer to architectural plans and specification for details
14/Oct/2026 02:46 PM
Question
:
1. CCTV - Could you please advise what the existing CCTV system is, as we have to match the existing for the new cameras.
2. Please confirm if we are to allow for hazmat testing for any items in the hazmat report as assumed positive prior to removal or if we are to allow for removal under full hazmat guidelines.
Thanks.
Answered on 19/Oct/2026 12:32 PM
:
1. CCTV - Existing CCTV system is Dahua
NVR:
DHI-NVR5432-16P-4KS2E
Cameras are Dahua NH-D30v6
(possibly a white label camera labelled Dahua)
2. HAZMAT - contractor to include removal and lawful disposal of all identified asbestos-containing and lead-affected materials, and provide occupational hygienist services, air monitoring (for over 10 m2 of non friable) and clearance certification are also to be included.
15/Oct/2026 04:44 PM
Question
:
Afternoon.
Regarding the Cart Shed. discrepancy item.
It stats Masonry,
Is there any option for a colour bond Shed, which be more affordable.
Answered on 19/Oct/2026 08:24 AM
:
Cart shed Masonry refers to the retaining wall. See Addendum 3 for detail.
14/Oct/2026 02:57 PM
Question
:
Please clarify the following tender items arising from Addendum 2:
1. Hazardous materials removal – Pricing Schedule V2 Item 1.06 / HAZMAT reports
Pricing Schedule V2 includes HAZMAT Removal within the Base Works. Please confirm whether the Head Contractor is to include removal and lawful disposal of all identified asbestos-containing and lead-affected materials, and whether occupational hygienist services, air monitoring and clearance certification are also to be included.
2. Mechanical package – Addendum 2 / Pricing Schedule V2 Items 18.01–18.03
Noting the public clarification that air-conditioning is required to the Pro Shop only, with the condenser location to follow, no updated Mechanical drawings or specification appear to be included in the Addendum 2 package. Please issue the updated Mechanical package or confirm the required tender pricing basis.
3. Hydrant Water Connection – Pricing Schedule V2 Items 28.01 and 28.03
The same Hydrant Water Connection description appears at Items 28.01 and 28.03. Please confirm whether both items are to be priced separately, or whether one item is duplicated and should not be separately priced.
4. Existing masonry repairs – S200-A / S210-A / S225-A
S200-A identifies one observed leaning/settled subfloor brick pier for reconstruction and requires structural-engineer inspection for any additional inadequate piers. Please confirm whether tenderers are to include only the known pier, with any additional piers priced by rate. Separately, S210-A / S225-A show new steelwork bearing on the existing 110 brick skin. Please confirm the number of bearing points and whether masonry make-good at those bearings is included in the masonry scope.
5. Discretionary Cart Shed masonry – Pricing Schedule V2 Item 27.04 / A-00-1000-C
Pricing Schedule V2 Item 27.04 requires separate pricing for Cart Shed masonry, however A-00-1000-C only notes “blockwork retaining walls as required” without dimensions. Please provide the required masonry dimensions/details or confirm the tender allowance basis.
Answered on 15/Oct/2026 04:02 PM
:
(edited on 15/Oct/2026 07:51 PM)
1. Hazardous materials removal – Pricing Schedule V2 Item 1.06 / HAZMAT reports
Pricing Schedule V2 includes HAZMAT Removal within the Base Works. Please confirm whether the Head Contractor is to include removal and lawful disposal of all identified asbestos-containing and lead-affected materials, and whether occupational hygienist services, air monitoring and clearance certification are also to be included.
ANS: Yes contractor to include removal and lawful disposal of all identified asbestos-containing and lead-affected materials, and yes occupational hygienist services, air monitoring (for over 10 m2 of non friable) and clearance certification are also to be included.
2. Mechanical package – Addendum 2 / Pricing Schedule V2 Items 18.01–18.03
Noting the public clarification that air-conditioning is required to the Pro Shop only, with the condenser location to follow, no updated Mechanical drawings or specification appear to be included in the Addendum 2 package. Please issue the updated Mechanical package or confirm the required tender pricing basis.
ANS:
Proshop
split system – 9KW
Condenser – Wall mounted in proshop wall facing clubhouse
Bar
Split System -5 KW
Condensor – Roof mounted
Dinning Room
Split Syetm – 9 Kw
Condenser – Roff mounted
3. Hydrant Water Connection – Pricing Schedule V2 Items 28.01 and 28.03
The same Hydrant Water Connection description appears at Items 28.01 and 28.03. Please confirm whether both items are to be priced separately, or whether one item is duplicated and should not be separately priced.
ANS: In Pricing Schedule V2
17.03 – Fire Hydrant – Refers to the actual fire hydrant associated works (excluding the water main connection in Beauchamp St)
28.03 – Fire Hydrant pipework (discretionary) – Refers to the water main pipework and connection. This includes connection to the water main in Beauchamp St and all associated pipework from the water main to the actual hydrant.
4. Existing masonry repairs – S200-A / S210-A / S225-A -
S200-A identifies one observed leaning/settled subfloor brick pier for reconstruction and requires structural-engineer inspection for any additional inadequate piers. Please confirm whether tenderers are to include only the known pier, with any additional piers priced by rate.
ANS: Relevant structural details provided .
Tenders to price the known pier and provide per pier rate for additional piers
Q: Separately, S210-A / S225-A show new steelwork bearing on the existing 110 brick skin. Please confirm the number of bearing points and whether masonry make-good at those bearings is included in the masonry scope.
ANS: 10 Bearing point of new deck steelwork.
Contractor shall allow for make good at these bearing points.
5. Discretionary Cart Shed masonry – Pricing Schedule V2 Item 27.04 / A-00-1000-C
Pricing Schedule V2 Item 27.04 requires separate pricing for Cart Shed masonry, however A-00-1000-C only notes “blockwork retaining walls as required” without dimensions. Please provide the required masonry dimensions/details or confirm the tender allowance basis.
ANS: Allow for a 7.5m W x 12mL cart shed and 1500mm high x 12m blockwork retaining wall length of the shed.
18/Oct/2026 11:38 AM
Question
:
Addendum 2 brought revised architectural, civil, structural and hydraulic documents, including updated schedules and roof plans. Several of our subcontractors are now re-pricing their packages on the revised documents, particularly roofing, hydraulics and civil works. We want to make sure Council receives a fully compliant, well-coordinated submission that reflects the current design.
We respectfully ask Council to consider a short extension of the closing date to Friday 23 October 2026 at 5:00 pm.
Answered on 19/Oct/2026 12:37 PM
:
Unfortunately due to the tight timing for Council Approval, the closing date and time will have to remain as 5pm Thursday 22 October 2026.
19/Oct/2026 02:50 PM
Question
:
Good afternoon,
Question from one of our contractors, for the structural steel works. Will the contractor used be required to have CC3 certification or will CC3 certification be done via a third party contractor?
Kind regards,
Answered on 22/Oct/2026 08:54 AM
:
Only CC2 fabricator category is required for this project. Our notes sheet shows CC3 but this can be relaxed.
Updates made to this Request
28/Sep/2026 02:09 PM
Please note: The following attachment has been recently added.
1. Added: Addendum_1 RFT-48.pdf
New Briefing date:
Thursday 1 October 2026 @ 8.30am .
Please consider this attachment when responding.
01/Oct/2026 03:06 PM
Please note: The following attachment has been recently added.
1. Added: RFT-48 Marrickville Golf Club_Upgrade_Pricing Schedule.xlsx
Please consider this attachment when responding.
06/Oct/2026 05:14 PM
We are finalising the full documentation package for RFT-48 Marrickville Golf Club Upgrade. The full, updated tender package will be released as soon as it is available before the end of this week.
Apologies for any inconvenience caused.
07/Oct/2026 08:27 AM
Dear tenderers - we are finalising the full documentation package for RFT-48 Marrickville Golf Club Upgrade, The full, updated tender package will be released by COB today 7/10/26.
08/Oct/2026 05:26 PM
Please note: The following attachment has been recently added.
1. Added: RFT-48 Addendum 2.zip
Please consider this attachment when responding.
15/Oct/2026 07:58 PM
Please note: The following attachments have been recently added.
1. Added: RFT-48 Addendum 3.zip
2. Added: RFT-48 Addendum 4.zip
Please consider these attachments when responding.
19/Oct/2026 04:02 PM
Please note: The following attachment has been recently added.
1. Added: RFT-48 Addendum 5.zip
Please consider this attachment when responding.
20/Oct/2026 09:36 PM
Please note: The following attachment has been recently added.
1. Added: Addendum_6 RFT-48.docx
Please consider this attachment when responding.