Tender Details
Power and Monitoring (Emu Park)
Business Name
Queensland Police Service
VP Reference #
VP455450
Buyers Reference #
QPS26346
Opens
Monday 19 May 2025
(E. Australia Standard Time)
Closes
Wednesday 28 May 2025 02:00 PM
(E. Australia Standard Time)
CLOSED
Supplier query cut-off
Tuesday 27 May 2025 02:00 PM
(E. Australia Standard Time)
Expected decision
Wednesday 04 June 2025
(E. Australia Standard Time)
Buyer Details
Business Name
Queensland Police Service
Location
40 Tank St
Brisbane City, Queensland 4000
Australia
WebSite:
https://www.police.qld.gov.au/
Business Info
Enhancing safety across Queensland stands as a fundamental commitment of the Queensland Police Service. Our focus remains on preventing, disrupting, and investigating matters affecting Queenslanders while strengthening our community engagement endeavours. Our goal is to instil a sense of security and trust, ensuring individuals feel empowered to rely on us for support whenever necessary.
Contact Name
Ross Davey
Position:
Senior Procurement Officer
Primary phone:
0405749711
Mobile phone:
0405749711
Fax number:
None Provided
Email:
davey.ross@police.qld.gov.au
What the buyer is requesting
Details
Supply and deliver the below equipment to:
Rockhampton Radio and Electronics Workshop
Cnr Musgrave and Armstrong Streets,
Rockhampton North,
QLD, 4701
• 5 x ICT Technologies 48v Power Supply / Charger with Changeover - Helios ICT800A-48SBC
• 6 x ICT - IP Monitored Smart Distribution Panel - Helios ICT200DB
• 72 x Circuit Breakers – 12 x 25A, 12 x 20A, 12 x 15A, 12 x 10A, 12 x 5A & 12 x 2A (Please advise if these sizes aren’t available)
• 5 x 48v to 12v isolated DC-DC Voltage Convertor – Must be compatible with the above ICT Circuit Breaker distribution unit and able to supply a minimum of 60A.
• 6 x O-Ring 26port switch - 12-48Vdc - RES-9242GCL-LV-NDUSTR, 26 Port Ethernet Switch
• 2 x Morningstar Solar regulator with monitoring - Morning Star MPPT - TS-MPPT-60
• 8 x Jinko 475W Solar Modules - Jinko - JKM475-N-60HL4-V - 475W Solar Module - Min Cap 450W
• 5 x Convertor - ICT Technologies 20-60v - 12v/100A Isolated Convertor - ICT206012-100AI2
Background information / Compatibility requirements
Details
Please ensure the following detail is included in your response
- Availability, Lead time.
- Part numbers and detailed descriptions.
- Delivery costs if applicable.
Desired Outcomes ('Nice to haves', Conditions & Warranties, SLA's, Project benefits)
Details
Delivery before Friday 20th June 2025.
Supplier lists selected
Lists
ELEC, Lighting, Equip & Services
Power Generation, Trans & Distrib.
Categories selected
Categories
Electrical Systems, Lighting, Equipment & Services
1: Batteries
2: Electrical Equipment & Components & Supplies
3: Switchboards & Switchgear
Power Generation & Transmission & Distribution
1: Photovoltaic Systems
2: Power Generation Systems
Regions of Service
Locations
Queensland
1: Brisbane
2: Far North
3: Fitzroy
4: Gold Coast
5: Mackay
6: Northern
7: Sunshine Coast
8: Wide Bay-Burnett
All Regions of Service locations are within Australia.
Information requested by others
20/May/2025 08:40 AM
Question
:
Hi,
please advise the characteristics of the circuit breakers i.e. voltage and curve requirements.
Answered on 20/May/2025 10:03 AM
:
The Breakers are to fit into a Dual Bus Breaker Panel, ICT200DB-12IRC.
We cannot change the current of the breakers. It must remain as stated.
Specification.
- Magnetic Hydraulic Circuit Breakers
- 65VDC rated
- Snap action rocker activation
- Built-in finger guards to prevent accidental actuating
- UL recognized, CSA, VDE, TUV, UL489A Listed (Telecom)
- Suitable for all ICT Distribution Series 3 dual bus breaker panels and Modular Power Series LDM
20/May/2025 09:11 AM
Question
:
Further to this, in place of the following:
12 x 15A - can these be 16A
12 x 5A - Can these be 6A
Answered on 20/May/2025 10:04 AM
:
The Breakers are to fit into a Dual Bus Breaker Panel, ICT200DB-12IRC.
We cannot change the current of the breakers. It must remain as stated.
Specification.
- Magnetic Hydraulic Circuit Breakers
- 65VDC rated
- Snap action rocker activation
- Built-in finger guards to prevent accidental actuating
- UL recognized, CSA, VDE, TUV, UL489A Listed (Telecom)
- Suitable for all ICT Distribution Series 3 dual bus breaker panels and Modular Power Series LDM
20/May/2025 03:35 PM
Question
:
Could you please clarify the below?
For ICT200DB : Please confirm if you are after ICT200DB-12 or ICT200DB-12IRC (Datasheet can be supplied for reference)
ICT206012-100AI2 : This part number has been obsolete and 35A is the max output current as specified in hardware datasheet; however, you can put 3 of them in parallel to get 100A
Answered on 22/May/2025 12:31 PM
:
Question 1 response:
The Breakers are to fit into a Dual Bus Breaker Panel, ICT200DB-12IRC.
We cannot change the current of the breakers. It must remain as stated.
Specification.
Magnetic Hydraulic Circuit Breakers
65VDC rated
Snap action rocker activation
Built-in finger guards to prevent accidental actuating
UL recognized, CSA, VDE, TUV, UL489A Listed (Telecom)
Suitable for all ICT Distribution Series 3 dual bus breaker panels and Modular Power Series LDM
Question 2 Response:
Please quote on 10 x 35A converters in place of the 5 100A units.
21/May/2025 02:43 PM
Question
:
Hi, please clarify part numbers and obsolesce concerns:
For:
- ICT200DB : Please confirm if you are after ICT200DB-12 or ICT200DB-12IRC
- 48VDC-12VDC isolated DC-DC Converter : What is the output current required
- ICT206012-100AI2 : This part number is obsolete. The current ITC offering is 35A max output we could put 3 together to get 100A, alternatively please propose an alternate brand/option that is acceptable.
- O-Ring 26port switch - 12-48Vdc - RES-9242GCL-LV-NDUSTR - model is obsolete/end-of-life - should we quote recommended replacment
Answered on 22/May/2025 12:35 PM
:
- ICT206012-70A12 - 48v to 12v DC Convertor units
- Please quote on 10 x 35A converters in place of the 5 100A units.
- Please provide source of eol information for the O-Ring switch.
22/May/2025 01:53 PM
Question
:
Thank you:
1. RES-9242GCL-LV-NDUSTR - Source of EOL is local distributor and manufacturer - new model is RES-P9242GCL-LV - Key difference in voltage input rage "Dual 24/48VDC (24~72VDC) power inputs"
2. Please advise - ICT200DB : Please confirm if you are after ICT200DB-12 or ICT200DB-12IRC
3. Further: ICT Hydraulic/Magnetic Circuit Breakers - 2A is EOL, 20A EOL, 5-, 10-, 15-, 25- and 30-Amp versions available - https://ict-power.com/product/hydraulic-magnetic-circuit-breakers/
Answered on 23/May/2025 01:03 PM
:
1. Please quote the new model RES-P9242GCL-LV, the change in voltage range will still allow us to operate effectively on the 48v system that is being installed.
2. ICT200DB-12IRC
3. Circuit Breakers - Please substitute 5A for 2A. And 25A for 20A.
Updates made to this Request
Updates
None...