Tender Details
Access this Tender
Texas STP pump and chlorine pre-fabricated buildings - Design, Supply, fit-out and installation
Business Name
Goondiwindi Regional Council
VP Reference #
VP524450
Buyers Reference #
RFT2627-19F
Opens
Monday 07 September 2026
(E. Australia Standard Time)
Closes
Wednesday 07 October 2026 04:00 PM
(E. Australia Standard Time)
Supplier query cut-off
Wednesday 07 October 2026 04:00 PM
(E. Australia Standard Time)
Expected decision
Sunday 06 December 2026
(E. Australia Standard Time)
Buyer Details
Business Name
Goondiwindi Regional Council
Location
McLean St
Goondiwindi, Queensland 4390
Australia
WebSite:
https://www.grc.qld.gov.au/
Business Info
Council provides residents with a wide range of services including road maintenance and construction; town planning and development controls; water and sewerage; waste collection and disposal; community cultural and recreational activities; library services; cemeteries; maintenance of parks and public areas.
OUR VISION To strengthen our thriving regional lifestyle and prosperous economy.
OUR MISSION To provide leadership in making locally-responsive and informed decisions, delivering quality services and facilities to the communities of the Goondiwindi region.
Contact Details
The buyer has elected to have their personal and contact details hidden. These details will be revealed at the buyers discretion.
What the buyer is requesting
Details
Goondiwindi Regional Council require the supply and installation including fitout of prefabricated buildings as part of the Texas Wastewater Treatment Plant (WWTP) Effluent Reuse Project.
Goondiwindi Regional Council invites Tenders from suitably qualified, experienced and resourced Contractors for the design, supply, fabrication, fit-out, delivery, installation and commissioning of the prefabricated buildings and associated infrastructure.
Attachments to this Request
Documents
11
Supplier lists selected
Lists
Building Products & Materials
Building Trade, Repairs, Maint.
Lab, Measure, Observe & Test Equip
Categories selected
Categories
Building Products & Materials
1: Prefabricated Buildings
Building Trade & Repairs & Maintenance Services
1: Water Treatment Services
Laboratory & Measuring & Observing & Testing Equip
1: Laboratory & Scientific Equipment
Regions of Service
Locations
Queensland
1: Darling Downs
All Regions of Service locations are within Australia.
Information requested by others
09/Sep/2026 10:03 AM
Question
:
Hi GRC
Can you advise if automation/scada integration scope is included in this package?
Thanks
Answered on 09/Sep/2026 10:24 AM
:
Hi,
SCADA programming and software integration are not included in this package. Physical installation and building-related provisions for the free-issued SCADA/control equipment are included as detailed in the Technical Specification. Tenderers are to review the Technical Specification for the full scope and associated interface requirements.
10/Sep/2026 04:41 PM
Question
:
Hello and greetings!
Given the coverage of the work scope, does the project tender have a mandatory site/online meeting? Kindly clarify. Thank you!
Answered on 11/Sep/2026 07:27 AM
:
Hi,
While there is no mandatory site meeting for these works, tenderers are welcome to request an inspection of the site.
Tenderers may nominate their preferred date and time, and Council will coordinate a suitable time. Once confirmed, the nominated time will be made available to all tenderers, with the details advised via the VendorPanel question portal.
Site visit requests are to be submitted via the VendorPanel question portal.
11/Sep/2026 11:23 AM
Question
:
P&ID-06 shows chlorine solution injected directly into the irrigation rising main, which operates against 85 m static head according to basis of design. This indicates a pressure of at least 8.3 bar before friction and terminal pressure. Assuming an injector differential pressure of 250 kPa, carrier water for the chlorination system needs to be supplied at approximately 11 bar or higher. The current PN12 solution pipework, 600 kPa instruments and undefined carrier-water pump duty do not appear suitable for this service.
Given the anticipated rising main pressure, can Council please advise whether the chlorine injection point may be relocated to the effluent pump suction, or whether the carrier water system and associated pipework should be upgraded to suit high-pressure injection into the rising main?
Answered on 14/Sep/2026 07:45 AM
:
Thank you for your query.
The carrier water system and associated pipework will be required to be upgraded to suit the higher pressure.
11/Sep/2026 12:37 PM
Question
:
Can GRC facilitate a site meeting for this project Tuesday 15th September?
Kind Regards,
Answered on 11/Sep/2026 01:58 PM
:
No site inspection will be undertaken as part of this tender package.
Tenderers are encouraged to review the available information and the 3D site view at the link below to familiarise themselves with the site and existing conditions:
Please note that civil works to be undertaken by others will result in changes to the site prior to commencement of these works. Tenderers should therefore consider the information provided with the RFT, together with the 3D site view, when preparing their tender.
16/Sep/2026 01:28 PM
Question
:
Good afternoon.
• Can the council please confirm that the prefabricated building contractor is to deliver and land the buildings onsite with all onsite mechanical and electrical connections of the buildings to be by others?
• Noting the below free issued items:
? Effluent Pump Station Main Switchboard
? Main Building SCADA/Control Panel
? Effluent Pump Set
Is the intention for the prefabricated building contractor to install these free issued items within the buildings or simply make space for them to be installed by others?
• Drawing DRG-STR-010 shows a space for analyser equipment. Can the council please confirm this analyser equipment is the “Chlorine Residual Analyser Panel” noted in DRG-PID-06?
Thanks in advance.
Answered on 17/Sep/2026 01:28 PM
:
1. Council confirms that the Contractor is to deliver and land the buildings onsite will all the electrical and mechanical connections to be done by other contractors.
2. The free issue items, Effluent Pump Station Main Switchboard, SCADA/Control Panel and Effluent Pump Set will be delivered to the Contractors site for installation. These items are to be installed at the Contractors workshop. The intent is to ensure no fabrication is done on site.
3. Correct, The Chlorine Residual Analyser Panel noted in PID-06 must be located as per STR-010 ('Analysers Equip').
21/Sep/2026 12:58 PM
Question
:
Good afternoon.
Can council please clarify flow and pressure requirements.
PID shows SCN 30001 with max flow of 66lps and model number SAF-X-4500.
this model cannot do that volume, Do we change model to suit 66lps, or assume lower flow rate and model is correct?
Also, design pressure states 10 bar. but pipe is specified in PN16.
Can we reduce the pipes to PN10?
thanks in advance?
Answered on 23/Sep/2026 09:56 AM
:
Thank you for the enquiry, please find the response below:
1. The system flowrate is 20 L/s, the SAF-X 4500 model is to remain.
2. Keep the pipework design to PN16.
3. The SAF-X-4500 design pressure in PN10 for continuous operation. This selection has been validated by the OEM.
Updates made to this Request
Updates
None...